This site uses strictly necessary cookies to work and to remember your privacy choices. With your permission it would also load content hosted by other services, such as videos, maps and fonts, which then receive your network address and device data. We do not sell or share your personal information and we run no advertising. Choose Accept all, Reject all or Customise. You can change your mind at any time through Privacy choices at the foot of every page.

  • Always on

    Needed for the site to work and to remember your privacy choices. Always on.

  • Remembers settings you choose, such as the light or dark display, in your browser.

  • Loads videos, maps and other content hosted by other services. Those services receive your address and device data.

Menu Close
In this section: Learn
Start
Guides
Domain packs
Participants
Security and privacy
Pilot kits
Operations
Ecosystem

Air quality: reference monitors and sensor networks

INFORMATIVE Source profiles/domains/air-quality/pack.yaml

On this page
  1. Observed properties
  2. Recommended quality tests
  3. Bindings and profiles
  4. Scenario: A city combines reference monitors with a co-located sensor network
  5. Sources
  6. Quality tests: example parameters

Informative: a domain pack is guidance for implementers. It adds no requirement, changes no schema and grants no conformance level. Several of the properties, bindings and profiles it names are proposed by draft proposals.

FieldValue
Statusinformative
Normativeno
Register domainsair-quality
Bindingslorawan, ogc-api, cap, wis2
ProfilesOBSP-NODE, OBSP-SITE, OBSP-COMMUNITY, OBSP-CONSUMER
Objects in the scenariosensor-passport, calibration-record, co-location-record, observation-record, quality-flag, alert-notice, product-manifest

Informative. This pack is guidance for implementers; it is not part of the specification, adds no requirement and grants no conformance level. The machine-readable form is pack.yaml, checked against ../pack.schema.json by tests/test_domain_packs.py.

Reference-method monitors and low-cost sensor networks that report particulate matter, nitrogen dioxide, ozone and related pollutants, with their quality tier (COMMUNITY profile, draft).

Observed properties

Ids from the observed-property register proposed by OIP-0006 (draft). Core: pm2_5_mass_concentration, pm10_mass_concentration, no2_mass_concentration, o3_mass_concentration, so2_mass_concentration, co_mass_concentration. Optional: pm1_mass_concentration, black_carbon_mass_concentration, nh3_mass_concentration, benzene_mass_concentration, particle_number_concentration, air_quality_index, mixing_layer_height, aerosol_optical_depth.

Example parameters only; an operator sets its own for each site and sensor and records them in the procedure. The test code is the protocol’s quality-flag test code.

Test Code Properties Unit
gross range RANGE pm2_5_mass_concentration, pm10_mass_concentration ug/m3
gross range RANGE no2_mass_concentration ug/m3
spike SPIKE pm2_5_mass_concentration ug/m3
flat line PERSISTENCE o3_mass_concentration ug/m3
internal consistency INTERNAL_CONSISTENCY pm2_5_mass_concentration, pm10_mass_concentration ug/m3
calibration validity CALIBRATION_VALIDITY pm2_5_mass_concentration, no2_mass_concentration ug/m3

Bindings and profiles

Bindings (proposed by draft proposals): lorawan, ogc-api, cap, wis2. Profiles: OBSP-NODE, OBSP-SITE, OBSP-COMMUNITY, OBSP-CONSUMER.

Scenario: A city combines reference monitors with a co-located sensor network

Low-cost sensors send PM2.5 and NO2 over LoRaWAN; each one first spends six weeks beside a reference monitor, and the co-location record holds the fit, the residuals and the validity window. Values inside the window are CALIBRATED, others INDICATIVE, and the reference monitors’ values are REFERENCE. The site cell runs range, spike and PM2.5-versus-PM10 checks. A public map reads all three tiers through the OGC API and draws them differently, and an episode alert is issued through CAP from the reference values only.

Objects: sensor-passport, calibration-record, co-location-record, observation-record, quality-flag, alert-notice, product-manifest.

Sources

  • CEN/TS 17660-1, Air quality: performance evaluation of air quality sensor systems, part 1 (gaseous pollutants) (not checked)
  • WHO global air quality guidelines (2021) (not checked)

Sources are cited by identifier only; no text, table or figure is reproduced, and none was checked for this pack.

Quality tests: example parameters

Example parameters only; an operator sets its own for each site and sensor.

TestCodePropertiesUnitExample parametersChecked
gross rangeRANGEobsp:prop:pm2_5_mass_concentration, obsp:prop:pm10_mass_concentrationug/m3failBelow: -5; failAbove: 2000not checked
gross rangeRANGEobsp:prop:no2_mass_concentrationug/m3failBelow: -5; failAbove: 1000not checked
spikeSPIKEobsp:prop:pm2_5_mass_concentrationug/m3suspect: 50; fail: 150not checked
flat linePERSISTENCEobsp:prop:o3_mass_concentrationug/m3windowHours: 4; tolerance: 0.5not checked
internal consistencyINTERNAL_CONSISTENCYobsp:prop:pm2_5_mass_concentration, obsp:prop:pm10_mass_concentrationug/m3rule: PM2.5 not above PM10 at the same inlet; tolerance: 2not checked
calibration validityCALIBRATION_VALIDITYobsp:prop:pm2_5_mass_concentration, obsp:prop:no2_mass_concentrationug/m3rule: a sensor value is CALIBRATED only inside the validity window of its co-location recordnot checked